Topic |
Rule |
Plot Level |
Plot Area |
For any Residential use, plot area shall be mini. 40.00 sq.mt and Mini. Plot Width shall be 3.50 mt.{Building Construction and Development By-Laws 2018, Rule No. 3.2.1 }
|
Plot Width |
For any Residential use, plot area shall be mini. 40.00 sq.mt and Mini. Plot Width shall be 3.50 mt.{Building Construction and Development By-Laws 2018, Rule No. 3.2.1 }
|
Plot Depth |
For any Residential use, plot area shall be mini. 40.00 sq.mt and Mini. Plot Width shall be 3.50 mt.{Building Construction and Development By-Laws 2018, Rule No. 3.2.1 }
|
Access Width |
For Existing BuitUp Area/Developed Area in Multi Residential Units, The width of the main abutting road shall not be less than 9.0 mt. {Building Construction and Development By-Laws 2018, Rule No. 26.2 and 26.3}
|
Plot Frontage |
For any Residential use, plot area shall be mini. 40.00 sq.mt and Mini. Plot Width shall be 3.50 mt.{Building Construction and Development By-Laws 2018, Rule No. 3.2.1 }
|
Coverage Area |
For Residential use, in location Existing Built Up Area/Developed Area ,if plot area is between 100-300 sq mt. then Max.Coverage shall be 65% applicable{Building Construction and Development By-Laws 2018, Rule No.3.5.1.(1)}
|
FAR Area |
(1)
For Residential use, in location Existing Built Up Area/Developed Area ,if plot area is between 100-300 sq mt. then Max.FAR shall be 1.75 applicable{Building Construction and Development By-Laws 2018, Rule No.3.5.1.(1)}
(2)
For Residential use, in location Existing Built Up Area/Developed Area ,if plot area is between 100-300 sq mt. then Max.FAR shall be 1.75 applicable{Building Construction and Development By-Laws 2018, Rule No.3.5.1.(1)}
(3)
In case of Constructed, Developed or New/ Undeveloped areas, purchasable FAR is permissible only if the plot is abutting a road of 18 m width or above {Rule No. 3.5.2.1}
|
Consumed FAR |
(1)
For Residential use, in location Existing Built Up Area/Developed Area ,if plot area is between 100-300 sq mt. then Max.FAR shall be 1.75 applicable{Building Construction and Development By-Laws 2018, Rule No.3.5.1.(1)}
(2)
For Residential use, in location Existing Built Up Area/Developed Area ,if plot area is between 100-300 sq mt. then Max.FAR shall be 1.75 applicable{Building Construction and Development By-Laws 2018, Rule No.3.5.1.(1)}
(3)
In case of Constructed, Developed or New/ Undeveloped areas, purchasable FAR is permissible only if the plot is abutting a road of 18 m width or above {Rule No. 3.5.2.1}
|
Tree Number |
For the residential Use, for plot area up to 200 sq.mt.,one tree shall be required. {As per Building Construction and Development By-Laws 2018, rule no. 3.1.2.2}
|
Equivalent Car Space Parking Check |
FOR RESIDENTIAL BUILDING, FOR PLOT AREA 100-200 SQ. MT. ONE CAR SHALL BE REQUIRED {AS PER BUILDING CONSTRUCTION AND DEVELOPMENT BY-LAWS 2018, RULE NO.3.10}
|
Total Car Parking Check |
FOR RESIDENTIAL BUILDING, FOR PLOT AREA 100-200 SQ. MT. ONE CAR SHALL BE REQUIRED {AS PER BUILDING CONSTRUCTION AND DEVELOPMENT BY-LAWS 2018, RULE NO.3.10}
|
Margin Rule |
For Row House,plot area above 150 and up to 300 sq. mt., min front 3.0, rear 3.0 shall be required and side margins are not required {Building Construction and Development By-Laws 2018,Rule No. 3.4.1 (I) , (VI)}
|
'' |
''
|
Building Level |
Building Height |
For Residencial Use, Maximum Height of construction shall be 10.50 mts (For Building without stilt/parking floor) from the level of the Building Unit.{Building Construction and Development By-Laws 2018, 3.4.1 }
|
Floor Height |
(1)
For Terrace floor, atleast 1.0 mt. high and max. upto 1.5 mt. ht. Parapet wall shall be provided {Building Construction and Development By-Laws 2018,}
(2)
For Terrace floor, atleast 1.0 mt. high and max. upto 1.5 mt. ht. Parapet wall shall be provided {Building Construction and Development By-Laws 2018,}
(3)
For any Habitable Floor, minimum Floor height shall be 2.75 mts.{Building Construction and Development By-Laws 2018,}
(4)
The plinth of the habitable area of any building shall be at a minimum height of 0.30mts from the established level of the building unit {Building Construction and Development By-Laws 2018, Rule No. 3.6.5, Page 51}
|
Floor Number |
For any Residential Single Dwelling unit without stilt Maximum Height of construction shall be 10.50 mts having max G+2 floor from the level of the Building Unit.{Building Construction and Development By-Laws 2018, 2.5.1.7 }
|
VShaft |
(1)
-
(2)
For Building upto 12.50 mt. Ht.,Size of Ventilation shaft shall be 2.80 sq.mt. with mini 1.20 mt. width {Building Construction and Development By-Laws 2018, Rule No.3.7.3}
|
StairCase Count |
For any building having more than one Ground floor, Mini. one staircase has to be provided
|
StairCase |
(1)
For Residential Building,stairwidth shall be mini. 1.0 mt. with max riser upto 0.19 mt. and min. tread upto 0.25 mt.{Building Construction and Development By-Laws 2018, Rule No.3.8.1, Page 54}
(2)
-
(3)
For nay Residential Building, The number of risers shall be 12.00 per flight for Stairs.{Building Construction and Development By-Laws 2018,}
(4)
For Residential Building,stairwidth shall be mini. 1.0 mt.,Cabinate Height shall be minimum 2.1 mt.{Building Construction and Development By-Laws 2018, Rule No.3.8.1, Page 54}
(5)
-
(6)
For nay Residential Building, The number of risers shall be 12.00 per flight for Stairs.{Building Construction and Development By-Laws 2018,}
|
Arch Projection |
(1)
-
(2)
-
(3)
For Building With stilt 12.5 mt. ht and without stilt 10.5 ht. Perm. width for Arh Proj/ Chhajja/ Balcony/ Roof Projection shall be 1.5 mt. or 1/2 of Prop. Open space (Whichever is less) and Perm. Area shall be Max. 10% open area {Rule No. 3.4.6 Page 42, 3.4.4 note, Page 40}
|
Building Level (Rooms) |
Balcony
|
No rule defined{Building Construction and Development By-Laws 2018, Rule No.3.6.1} |
Bed Room
|
Minimum size of Any habitable room shall be 9.50 sq. mt.{Building Construction and Development By-Laws 2018, Rule No.3.6.1} |
Kitchen
|
Minimum size of Kitchen room shall be 5.00 sq. mt.{Building Construction and Development By-Laws 2018,} |
Lounge
|
No rule defined{Building Construction and Development By-Laws 2018, Rule No.3.6.1} |
Study Room
|
Minimum size of Any habitable room shall be 9.50 sq. mt.{Building Construction and Development By-Laws 2018, Rule No.3.6.1} |
Toilet
|
Minimum size of Bath +WC room shall be 2.80 sq. mt.{Building Construction and Development By-Laws 2018} |